Coordination of directional overcurrent and distance relays based on nonlinear multivariable optimization

To ensure stability, security, and protection of electrical equipment from the damage the suitable coordination must be made in interconnected networks. In this paper, the nonlinear multivariable optimization techniques have been used with different performance indexes: Sequential quadratic programm...

Full description

Saved in:
Bibliographic Details
Main Authors: Abd Almuhsen, Tahseen Ali (Author), Sultan, Ahmed Jasim (Author)
Format: EJournal Article
Published: Institute of Advanced Engineering and Science, 2020-03-01.
Subjects:
Online Access:Get fulltext
Tags: Add Tag
No Tags, Be the first to tag this record!
LEADER 02576 am a22003013u 4500
001 ijeecs19285_13497
042 |a dc 
100 1 0 |a Abd Almuhsen, Tahseen Ali  |e author 
100 1 0 |e contributor 
700 1 0 |a Sultan, Ahmed Jasim  |e author 
245 0 0 |a Coordination of directional overcurrent and distance relays based on nonlinear multivariable optimization 
260 |b Institute of Advanced Engineering and Science,   |c 2020-03-01. 
500 |a https://ijeecs.iaescore.com/index.php/IJEECS/article/view/19285 
520 |a To ensure stability, security, and protection of electrical equipment from the damage the suitable coordination must be made in interconnected networks. In this paper, the nonlinear multivariable optimization techniques have been used with different performance indexes: Sequential quadratic programming (SQP), Sequential quadratic programming legacy (SQP-Legacy), Interior-Point and Active-Set for IEEE- 8 bus test system.  This system consists of twenty-eight protective relays divided into fourteen directional overcurrent relays (DOCR) and fourteen distance relays (DR). It has been tested in the ETAP environment to obtain three-phase short circuit current at the near and far end faults and operating time for all DOC relays for near-end fault as well as test the second zone time for distance relays (TZ2) with pilot signal (WP)and without pilot signal (WOP) of the proposed algorithm was used to reduce overall operating time of DOC relays and obtain optimal values for time multiplier setting (TMS) and TZ2 with the different coordination time interval (CTI) between main and backup relays. The simulation results were validated in ETAP program prove that the effectiveness of the Active-Set to minimize the TMS and TZ2 for the system. 
540 |a Copyright (c) 2019 Institute of Advanced Engineering and Science 
540 |a http://creativecommons.org/licenses/by-nc/4.0 
546 |a eng 
690
690 |a Nonlinear multivariable optimization; PUTT; Pilot protection; Directional overcurrent relay; Distane relay 
655 7 |a info:eu-repo/semantics/article  |2 local 
655 7 |a info:eu-repo/semantics/publishedVersion  |2 local 
655 7 |2 local 
786 0 |n Indonesian Journal of Electrical Engineering and Computer Science; Vol 17, No 3: March 2020; 1194-1205 
786 0 |n 2502-4760 
786 0 |n 2502-4752 
786 0 |n 10.11591/ijeecs.v17.i3 
787 0 |n https://ijeecs.iaescore.com/index.php/IJEECS/article/view/19285/13497 
856 4 1 |u https://ijeecs.iaescore.com/index.php/IJEECS/article/view/19285/13497  |z Get fulltext